MODBUS学习笔记——modbus tk modbus TCP主机实现
# -*- coding: utf_8 -*- import sys import logging import modbus_tk import modbus_tk.defines as cst import modbus_tk.modbus_tcp as modbus_tcp logger = modbus_tk.utils.create_logger("console") if __name__ == "__main__": try: # 连接MODBUS TCP从机 master = modbus_tcp.TcpMaster(host="192.168.1.15") master.set_timeout(5.0) logger.info("connected") # 读保持寄存器 logger.info(master.execute(1, cst.READ_HOLDING_REGISTERS, 0, 16)) # 读输入寄存器 logger.info(master.execute(1, cst.READ_INPUT_REGISTERS, 0, 16)) # 读线圈寄存器 logger.info(master.execute(1, cst.READ_COILS, 0, 16)) # 读离散输入寄存器 logger.info(master.execute(1, cst.READ_DISCRETE_INPUTS, 0, 16)) # 单个读写寄存器操作 # 写寄存器地址为0的保持寄存器 logger.info(master.execute(1, cst.WRITE_SINGLE_REGISTER, 0, output_value=21)) logger.info(master.execute(1, cst.READ_HOLDING_REGISTERS, 0, 1)) # 写寄存器地址为0的线圈寄存器,写入内容为0(位操作) logger.info(master.execute(1, cst.WRITE_SINGLE_COIL, 0, output_value=0)) logger.info(master.execute(1, cst.READ_COILS, 0, 1)) # 多个寄存器读写操作 # 写寄存器起始地址为0的保持寄存器,操作寄存器个数为4 logger.info(master.execute(1, cst.WRITE_MULTIPLE_REGISTERS, 0, output_value=[20,21,22,23])) logger.info(master.execute(1, cst.READ_HOLDING_REGISTERS, 0, 4)) # 写寄存器起始地址为0的线圈寄存器 logger.info(master.execute(1, cst.WRITE_MULTIPLE_COILS, 0, output_value=[0,0,0,0])) logger.info(master.execute(1, cst.READ_COILS, 0, 4)) except modbus_tk.modbus.ModbusError, e: logger.error("%s- Code=%d" % (e, e.get_exception_code()))
slaver
|
从机地址
|
modbus TCP时可以忽略该参数
|
function_code
|
功能码 |
modbus_tk.modbus_tcp中定义
|
starting_address
|
寄存器起始地址
|
可设定
|
quantity_of_x
|
寄存器数量
|
可设定
|
output_value
|
输出内容
|
读操作是无效,写操作是输入为List类型
|